Newshot

Protection-Oriented Assessment of Machine Learning-Based Fault Detection in Power Systems

Summary

arXiv:2611.17872v1 Announce Type: new Abstract: Machine learning (ML)-based fault detectors are increasingly proposed for power system protection, yet aggregate metrics can obscure the consequences of false and missed trips. We present a protection-oriented assessment of three ML detectors and a sequence-current reference on PROTECT-90, comprising 9,022 simulated fault episodes on a 90 kV double-circuit line. The assessment combines five window conditions, causal window-end labelling, episode-grouped cross-validation, and operating-point selection under a fixed security budget. It reports security, dependability, detection timing, decision margins, and episode-level nuisance assertions. Gradient-boosted trees, a convolutional neural network, and logistic regression achieve AUC-ROC values above 0.999, yet at a security budget of $10^{-3}$ their developed-fault missed-trip rates range from 0.007% to 1.99%. Post-clearing false-trip rates of approximately 0.12-0.16% per window coexist with…

This source only provides a headline — there is no body to show. Use “Read the original” below to read it at the source.

Published by arXiv cs.LG
This site only summarises and aggregates; copyright stays with the original author. Headlines and summaries follow the source — where they differ, the original wins.